NFPA 25 inspection, testing and maintenance frequencies.

Every item in the seven summary tables of NFPA 25 (2023): sprinkler systems, standpipes, fire pumps, water storage tanks, water spray, water mist and valves, with its minimum frequency and the section behind it. Filter by system, by task, by how often, or search for the component. Free from FireInspection360, the fire prevention platform built by fire inspectors.

No registration needed for the demo site.
A firefighter's helmet

How often does NFPA 25 require it?

Tables 5.1.1.2, 6.1.1.2, 8.1.1.2, 9.1.1.2, 10.1.1.2, 12.1.1.2 and 13.1.1.2 of NFPA 25, 2023 edition, 335 items. A dash in the standard means the frequency is set in the referenced section; that section is named here.

335 of 335 items.
Chapter 5: Sprinkler System (Table 5.1.1.2)
Inspection
ItemFrequencyReference
Assessment of the internal piping condition See Chapter 14 Chapter 14
Automatic air vents Annually Chapter 13
Control valves See Chapter 13 Chapter 13
Electrically operated sprinklers Annually 5.2.1.5
Fire department connections See Chapter 13 Chapter 13
Gauges (wet and deluge systems) See Chapter 13 Chapter 13
Gauges (dry and preaction systems) See Chapter 13 Chapter 13
Hangers/braces/supports Annually 5.2.3
Heat tracing See 5.2.6 5.2.6
Hydraulic design information sign Annually 5.2.5
Information signs Annually 5.2.7, 5.2.8, and 5.2.9
Pipe and fittings Annually 5.2.2
Sprinklers Annually 5.2.1
Sprinklers (spare) Annually 5.2.1.4
Sprinkler guards Annually 5.2.1.1.7
Supervisory signal devices (except valve supervisory switches) See 5.2.4 and Chapter 13 5.2.4 and Chapter 13
System valves See Chapter 13 Chapter 13
Valve supervisory signal devices See 5.2.4 and Chapter 13 5.2.4 and Chapter 13
Waterflow alarm devices See 5.2.4 and Chapter 13 5.2.4 and Chapter 13
Test
ItemFrequencyReference
Antifreeze solution Annually 5.3.4
Control valves See Chapter 13 Chapter 13
Electrically operated sprinklers See 5.3.2 5.3.2
Gauges See Chapter 13 Chapter 13
Main drain See Chapter 13 Chapter 13
Sprinklers (all) At 50 years and every 10 years thereafter 5.3.1
Sprinklers (all) At 75 years and every 5 years thereafter 5.3.1
Sprinklers (dry) At 20 years and every 10 years thereafter 5.3.1
Sprinklers (extra-high or greater temperature solder type) Every 5 years 5.3.1
Sprinklers (fast-response, except ESFR and CMSA) At 25 years and every 10 years thereafter 5.3.1
Sprinklers (ESFR and CMSA with fast-response elements) At 20 years and every 10 years thereafter 5.3.1
Sprinklers (harsh environments) Every 5 years 5.3.1
Supervisory signal devices (except valve supervisory switches) See Chapter 13 Chapter 13
System valves See Chapter 13 Chapter 13
Valve supervisory signal devices See Chapter 13 Chapter 13
Waterflow alarm devices See 5.3.3 and Chapter 13 5.3.3 and Chapter 13
Maintenance
ItemFrequencyReference
Low-point drains (dry pipe and preaction systems) See Chapter 13 Chapter 13
Sprinklers and automatic spray nozzles protecting commercial cooking equipment and ventilation systems Annually 5.4.1.8
Replacement of sprinklers manufactured prior to 1920 See 5.4.1.1 5.4.1.1
Replacement of sprinklers showing signs in 5.2.1.1.1 See 5.4.1.1 5.4.1.1
Replacement of sprinklers with unsatisfactory performance See 5.4.1.1 5.4.1.1
Replacement of sprinklers affected by a fire See 5.4.1.1 5.4.1.1
Replacement of threaded sprinklers removed from fitting for any reason (except dry type) See 5.4.1.2 5.4.1.2
Replacement of damaged sprinkler guards See 5.2.1.1.7.2 5.2.1.1.7.2
Valves (all types) See Chapter 13 Chapter 13
Investigation
ItemFrequencyReference
Obstruction See Chapter 14 Chapter 14
Chapter 6: Standpipe and Hose Systems (Table 6.1.1.2)
Inspection
ItemFrequencyReference
Cabinet Annually 6.2.8
Control valves See Chapter 13 Chapter 13
Gauges See Chapter 13 Chapter 13
Hose Annually 6.2.5
Hose connection Annually 6.2.3
Hose nozzle Annually and after each use 6.2.6
Hose storage device Annually 6.2.7
Hydraulic design information sign Annually 6.2.2
Hose valves See Chapter 13 Chapter 13
Piping Annually 6.2.4
Pressure-regulating devices See Chapter 13 Chapter 13
Supervisory devices (except valve supervisory devices) See Chapter 13 Chapter 13
Valve supervisory devices See Chapter 13 Chapter 13
Test
ItemFrequencyReference
Control valves See Chapter 13 Chapter 13
System valves See Chapter 13 Chapter 13
Flow test 5 years 6.3.1
Hose See NFPA 1962 NFPA 1962
Hose connection pressure regulating devices See Chapter 13 Chapter 13
Hose valves See Chapter 13 Chapter 13
Hydrostatic test (manual and semiautomatic dry standpipes) 5 years 6.3.2
Main drain test See Chapter 13 Chapter 13
Pressure control valve See Chapter 13 Chapter 13
Pressure-reducing valve See Chapter 13 Chapter 13
Supervisory signal devices (except valve supervisory switches) See Chapter 13 Chapter 13
Valve status test See Chapter 13 Chapter 13
Valve supervisory devices See Chapter 13 Chapter 13
Waterflow alarm devices See Chapter 13 Chapter 13
Maintenance
ItemFrequencyReference
Hose valves See Chapter 13 Chapter 13
Pressure gauges See Chapter 13 Chapter 13
Valves (all types) Annually/as needed Chapter 13
Chapter 8: Fire Pump (Table 8.1.1.2)
Inspection
ItemFrequencyReference
Alignment Annually 8.3.6.4
Cable/wire insulation Annually 8.1.1.2.5
Diesel engine system Weekly 8.2.2(4)
Electric system Weekly 8.2.2(3)
Engine crankcase breather Quarterly 8.1.1.2.12
Exhaust system, drain condensate trap, and silencers Annually 8.1.1.2.13
Flexible hoses and connections Annually 8.1.1.2.11
Fuel tank vents and overflow Annually 8.1.1.2.10
Plumbing parts - inside and outside of panels Annually 8.1.1.2.6
Printed circuit board (PCB) corrosion Annually 8.1.1.2.4
Pump Weekly 8.2.2(2)
Pump house/room Weekly 8.2.2(1)
Shaft movement or endplay while running Annually 8.1.1.2.1
Steam pump system Weekly 8.2.2(5)
Suction screens Annually 8.3.3.16
Test
ItemFrequencyReference
Automatic transfer switch and emergency/standby generators Per NFPA 110 8.3.6.2
Diesel engine–driven fire pump (no flow) Weekly 8.3.1.1
Diesel fuel testing Annually 8.3.4.1
Electric motor–driven fire pump (no flow) Weekly/monthly 8.3.1.2
Electronic control module (ECM) Annually 8.3.3.17
Fire pump alarm signals Annually 8.3.3.14
Flow meters Annually 8.3.3.5.3
Fuel tank, float switch, and supervisory signal for interstitial space Quarterly 8.1.1.2.7
Gauges, transducers, and other devices used for testing Annually 8.3.3.5.2
Main pressure relief valve Annually 8.3.3.12, 13.5.6.2.3
Pump house/room environmental conditions See 8.3.6.3 8.3.6.3
Pump operation (no flow) Weekly/monthly 8.3.2, 8.3.5
Pump performance (flow) Annually 8.3.3, 8.3.5
Supervisory signal for high cooling water temperature Annually 8.1.1.2.8
Maintenance
ItemFrequencyReference
Batteries Annually 8.1.1.2.15
Circulating water filter Annually 8.1.1.2.22
Control and power wiring connections Annually 8.1.1.2.16
Controller and all other components of the pump assembly Per manufacturer 8.5
Diesel active fuel maintenance system Annually or per manufacturer 8.3.4.3
Diesel engine system Per manufacturer 8.5
Electric motor and power system Per manufacturer 8.5
Electrical connections Annually 8.1.1.2.2
Engine lubricating oil 50 operating hours or annually 8.1.1.2.17
Engine oil filter 50 operating hours or annually 8.1.1.2.18
Fuel filter 50 operating hours or annually 8.1.1.2.19
Fuel tank - check for water and foreign materials Annually 8.1.1.2.9
Measure back pressure on engine turbo Annually 8.1.1.2.14
Power transmission components with elastomeric materials (including torsional couplings) 5 years or per manufacturer 8.1.1.2.24
Pressure gauges and sensors Annually 8.1.1.2.23
Pump and motor bearings and coupling Annually or as required 8.1.1.2.3
Sacrificial anode Annually 8.1.1.2.21
Chapter 9: Water Storage Tank (Table 9.1.1.2)
Inspection
ItemFrequencyReference
Catwalks and ladders Quarterly 9.2.4.1
Check valves See Chapter 13 Chapter 13
Control valves See Chapter 13 Chapter 13
Expansion joints Annually 9.2.4.3
Foundation Quarterly 9.2.4.1
Heating system - tanks with supervised low-temperature alarms connected to constantly attended location Quarterly 9.2.2.1
Heating system - tanks without supervised low-temperature alarms connected to constantly attended locationCold weather/heating season only Daily 9.2.2.2
Hoops and grillage Annually 9.2.4.4
Interior - all other tanks 5 years 9.2.5.1.2
Interior - steel tanks without corrosion protection 3 years 9.2.5.1.1
Painted, coated, or insulated surfaces Annually 9.2.4.5
Support structure Quarterly 9.2.4.1
Surrounding area Quarterly 9.2.4.2
Tank - exterior Quarterly 9.2.4.1
Temperature alarms - connected to constantly attended locationCold weather/heating season only Quarterly 9.2.3.2
Temperature alarms - not connected to constantly attended locationCold weather/heating season only Weekly 9.2.3.3
Vents Quarterly 9.2.4.1
Water level - tanks equipped with supervised water-level alarms connected to constantly attended location Quarterly 9.2.1.1
Water level - tanks without supervised water-level alarms connected to constantly attended location Monthly 9.2.1.2
Test
ItemFrequencyReference
High-temperature limit switches Prior to heating season 9.3.4
Level indicators 5 years 9.3.1
Low-water temperature alarms Prior to heating season 9.3.3
Pressure gauges See Chapter 13 Chapter 13
Tank heating system Prior to heating season 9.3.2
Valve status test See Chapter 13 Chapter 13
Water-level signals (high and low) Annually 9.3.5
Maintenance
ItemFrequencyReference
Check valves See Chapter 13 Chapter 13
Control valves See Chapter 13 Chapter 13
Embankment-supported coated fabric (ESCF) 2 years or per manufacturer 9.4.6.2
Water level See 9.4.2 9.4.2
Chapter 10: Water Spray Fixed System (Table 10.1.1.2)
Inspection
ItemFrequencyReference
Backflow preventer See Chapter 13 Chapter 13
Check valves See Chapter 13 Chapter 13
Control valves See Chapter 13 Chapter 13
Deluge valve See Chapter 13 Chapter 13
Detection systems and components See NFPA 72 NFPA 72
Detector check valves See Chapter 13 Chapter 13
Drainage Quarterly 10.2.7
Fire pump system See Chapter 8 Chapter 8
Fittings Annually 10.2.3, 10.2.3.1
Fittings (rubber-gasketed) Annually and after each system activation 10.2.3.1
Gravity tanks See Chapter 9 Chapter 9
Hangers, braces, and supports Annually and after each system activation 10.2.3.2
Heat (deluge valve house) See Chapter 13 Chapter 13
Nozzles Annually and after each system activation 10.2.4
Piping Annually and after each system activation 10.2.3.1
Pressure tank See Chapter 9 Chapter 9
Strainers (mainline) Annually and after each system activation 10.2.6
Strainers (others) Per manufacturer's instructions 10.2.6
Suction tanks See Chapter 9 Chapter 9
Water supply piping See 10.2.5.2 10.2.5.2
UHSWSS - controllers Start of each shift 10.4.3
UHSWSS - detectors Monthly 10.4.2
UHSWSS - valves Start of each shift 10.4.4
Test
ItemFrequencyReference
Backflow preventer See Chapter 13 Chapter 13
Check valves See Chapter 13 Chapter 13
Control valves See Chapter 13 Chapter 13
Deluge valve See Chapter 13 Chapter 13
Detection systems See NFPA 72 NFPA 72
Detector check valve See Chapter 13 Chapter 13
Fire pump system See Chapter 8 Chapter 8
Gravity tanks See Chapter 9 Chapter 9
Main drain test See Chapter 13 Chapter 13
Manual release Annually 10.3.5
Nozzles Annually 10.3
Pressure tank See Chapter 9 Chapter 9
Strainers Annually 10.2.6
Suction tanks See Chapter 9 Chapter 9
Waterflow alarm See Chapter 13 Chapter 13
Water spray system test See Chapter 13 Chapter 13
Water supply flow test See Chapter 7 Chapter 7
UHSWSS Annually 10.4
Valve status test See Chapter 13 Chapter 13
Maintenance
ItemFrequencyReference
Backflow preventer See Chapter 13 Chapter 13
Check valves See Chapter 13 Chapter 13
Control valves See Chapter 13 Chapter 13
Deluge valve See Chapter 13 Chapter 13
Deluge valve enclosures See Chapter 4 Chapter 4
Detection systems See NFPA 72 NFPA 72
Detector check valve See Chapter 13 Chapter 13
Fire pump system See Chapter 8 Chapter 8
Gravity tanks See 10.2.9, Chapter 9 10.2.9, Chapter 9
Pressure tank See 10.2.9, Chapter 9 10.2.9, Chapter 9
Strainers Annually 10.2.1.4, 10.2.1.6, 10.2.6
Strainers (baskets/screen) 5 years 10.2.1.4, 10.2.1.7, A.10.2.6
Suction tanks See Chapter 9 Chapter 9
Water spray nozzles Annually 10.2.4
Chapter 12: Water Mist System (Table 12.1.1.2)
Inspection
ItemFrequencyReference
Additive storage cylinders Quarterly/semiannually 12.2.7
Air compressors and receivers See Chapter 13 Chapter 13
Backflow preventers See Chapter 13 Chapter 13
Compressed gas storage cylinders, hoses, support, and restraint Quarterly/annually/every 5 years 12.2.5.1.1, 12.2.5.2, 12.2.5.3, 12.2.5.9
Compressed gas storage cylinder valve and pressure Semiannually/annually 12.2.5.4, 12.2.5.4.1, 12.2.5.4.2, 12.2.5.8
Control equipment See NFPA 72 NFPA 72
Detection systems See NFPA 72 NFPA 72
Enclosure features, interlocks Semiannually 12.2.11
Fire pump system See Chapter 8 Chapter 8
Gauges (piping system) See Chapter 13 Chapter 13
Hangers, braces, and supports Annually and after each system discharge or activation 12.2.4
Internal piping conditions See Chapter 14 Chapter 14
Nozzles Annually and after each system discharge or activation 12.2.1
Pneumatically operated valves and tubing Semiannually 12.2.6
Pneumatically operated standby pumps Monthly 12.2.9
Strainers and filters After each system discharge or activation 12.2.2
System control valves See Chapter 13 Chapter 13
System piping, tubing, and fittings Annually and after each system discharge or activation 12.2.3
Water recirculation tanks Monthly/quarterly/annually 12.2.8
Water storage cylinders (high pressure) Quarterly/semiannually/annually 12.2.5.1.2, 12.2.5.4, 12.2.5.4.3, 12.2.5.5, 12.2.5.6, 12.2.5.7, 12.2.5.8
Water storage tanks See Chapter 9 Chapter 9
Water supply Quarterly/annually 12.2.10
Test
ItemFrequencyReference
Additives and injection system Annually 12.3.4, 12.3.5
Air compressors and receivers Annually Chapter 13
Backflow preventers See Chapter 13 Chapter 13
Compressed gas storage cylinder 5–12 years 12.3.6
Control equipment See 12.3.7 12.3.7
Detection systems See 12.3.8 12.3.8
Fire pump system See Chapter 8, 12.3.9 Chapter 8, 12.3.9
Gauges (piping system) See Chapter 13 Chapter 13
Hoses 5 years 12.3.10
Interlocks Annually 12.3.11
Nozzles, automatic At 10 years and every 5 years thereafter 12.3.1.2
Nozzles, automatic (harsh environments) At 5 years and every 5 years thereafter 12.3.1.3
Nozzles, open At 10 years and every 5 years thereafter 12.3.2.3
Nozzles, open (harsh environments) Annually 12.3.2.2
Pneumatic valves Semiannually 12.3.12
Pneumatic valve solenoid releases Annually 12.3.13
Pneumatically operated standby pumps Annually 12.3.14
Strainers and filters Annually 12.3.3
System control valves Annually 12.3.15
Water mist system Annually 12.3.16
Water recirculation tanks Annually 12.3.17
Water storage cylinders (high pressure) 5–12 years 12.3.18
Water storage tanks See 12.3.19 12.3.19
Water supply Annually 12.3.20
Maintenance
ItemFrequencyReference
Air compressors and receivers See Chapter 13 Chapter 13
Backflow preventers See Chapter 13 Chapter 13
Control equipment See NFPA 72 NFPA 72
Detection systems See NFPA 72 NFPA 72
Fire pump system See Chapter 8 Chapter 8
Pneumatically operated standby pumps Every 5 years 12.4.3
Strainers and filters Annually and after each system discharge 12.2.2
Water mist system Annually 12.4.1
Water tanks Annually 12.4.1
Chapter 13: Valves, Valve Components, and Trim (Table 13.1.1.2)
Inspection
ItemFrequencyReference
Alarm valves
Exterior Quarterly 13.4.1.1
Interior 5 years 13.4.1.2
Strainers, filters, orifices 5 years 13.4.1.2
Backflow prevention assemblies
Reduced pressure Weekly 13.7.1
Reduced-pressure detectors Weekly 13.7.1
Interior 5 years 13.7.1.3
Check valves
Interior 5 years 13.4.2.1
Control valves
All valves except locked or supervised Weekly 13.3.2.1
Locked or supervised Monthly 13.3.2.1.1
Electrically supervised Quarterly 13.3.2.1.2
Dry pipe valves/quick-opening devices
Enclosure (during cold weather) See Chapter 4 Chapter 4
Exterior Monthly 13.4.5.1.2
Interior Annually 13.4.5.1.3
Strainers, filters, orifices 5 years 13.4.5.1.4
Low temperature alarm Annually Chapter 4
Deluge valves
Enclosure (during cold weather) Daily/weekly Chapter 4
Exterior Monthly 13.4.4.1.1
Interior Annually/5 years 13.4.4.1.2
Strainers, filters, orifices 5 years 13.4.4.1.3
Fire department connections Quarterly 13.8.1
Gauges Monthly/quarterly 13.2.4
Hose valves Quarterly 13.6.1
Preaction valves
Enclosure (during cold weather) See Chapter 4 Chapter 4
Exterior Monthly 13.4.3.1.1
Interior Annually/5 years 13.4.3.1.2
Strainers, filters, orifices 5 years 13.4.3.1.3
Pressure-regulating and relief valves
Master pressure regulating Weekly 13.5.4.1
Sprinkler system pressure reducing Quarterly 13.5.1.1
Hose connection pressure regulating Annually 13.5.2.1
Hose rack pressure regulating Annually 13.5.3.1
Fire pump circulation relief With no flow test 13.5.6.1
Fire pump main pressure-relief With fire pump test 13.5.6.2
Valve supervisory signal initiating device Quarterly 13.3.2.1.3
Supervisory signal devices (except valve supervisory switches) Quarterly 13.2.5.1
Air compressors and nitrogen generators Monthly 13.10.2
Waterflow alarms Quarterly 13.2.3
Test
ItemFrequencyReference
Backflow prevention assemblies Annually 13.7.2
Control valves
Operation and position Annually 13.3.3.1
Valve status test After the control valve closed and reopened 13.3.3.4
Supervisory Semiannually 13.3.3.5
Deluge valves
Trip test Annually/3 years 13.4.4.2.3
Dry pipe valves/quick-opening devices
Air leakage 3 years 13.4.5.2.9
Priming water Quarterly 13.4.5.2.1
Low air pressure alarm Annually 13.4.5.2.6
Quick-opening devices Quarterly 13.4.5.2.4
Trip test Annually 13.4.5.2.2
Full-flow trip test 3 years 13.4.5.2.2.2
Gauges 5 years 13.2.4.2
Main drains Annually/quarterly 13.2.2
Preaction valves
Priming water Quarterly 13.4.3.2.1
Low air pressure alarms Quarterly 13.4.3.2.11
Trip test Annually/3 years 13.4.3.2.2 and 13.4.3.2.3
Air leakage 3 years 13.4.3.2.6
Low temperature alarm Annually 13.4.3.2.12
Pressure-regulating and relief valves
Master pressure regulating Quarterly/annually 13.5.4.2 and 13.5.4.3
Sprinkler systems pressure reducing Annually/5 years 13.5.1.3 and 13.5.1.2
Hose connection pressure regulating Annually/5 years 13.5.2.3 and 13.5.2.2
Hose rack pressure regulating Annually/5 years 13.5.3.3 and 13.5.3.2
Fire pump circulation relief With churn test 13.5.6.1.2
Fire pump pressure relief valves With fire pump test 13.5.6.2.3
Air compressors and nitrogen generators Annually 13.10.3
Hose valves Annually/3 years 13.6.2
Waterflow alarms Semiannually 13.2.3
Supervisory signal devices (except valve supervisory switches) Annually 13.2.5.2
Maintenance
ItemFrequencyReference
Alarm valves Per manufacturer 13.4.1.3
Backflow prevention assemblies Per manufacturer 13.7.3
Check valves Per manufacturer 13.4.2.2
Control valves (outside screw and yoke) Annually 13.3.4
Deluge valves Annually/5 years 13.4.4.3
Dry pipe valves/quick-opening devices Annually 13.4.5.3
Hose valves As needed 13.6.3
Preaction valves Annually/5 years 13.4.3.3
Air compressors and nitrogen generators Per manufacturer 13.10.4
Summarized from NFPA 25, 2023 edition. NFPA 25 is a copyrighted standard of the National Fire Protection Association; these are the minimum frequencies its summary tables list, the referenced sections carry the conditions, and the edition your jurisdiction adopted, the authority having jurisdiction and the manufacturer's instructions govern.
How it works

A sprinkler system is only as good as its last test.

NFPA 25 is the standard for the inspection, testing and maintenance of water-based fire protection systems, and it is written for the building owner: the owner is responsible for keeping the system in working order, and the standard sets the minimum frequencies at which each component is looked at, tested or serviced. Each chapter opens with a summary table, and those tables are what a contractor's inspection report, a fire marshal's ITM program and a property manager's calendar are built from. Control valves are inspected weekly unless they are locked or electrically supervised; gauges monthly on a wet system; waterflow alarms tested semiannually; the main drain annually; the fire pump run weekly or monthly with a full flow test once a year; sprinklers themselves sampled at 50 years and every 10 after that, sooner for dry, fast response and harsh environment heads.

Two readings of the table cause most of the confusion. A dash in the frequency column does not mean no frequency: it means the frequency is set in the referenced section, usually Chapter 13 for anything that is a valve or a gauge, and this page names that section beside every dash. And a frequency printed as "annually/5 years" is two rules for two parts of the same component, the section explaining which is which. The frequencies are minimums; the authority having jurisdiction, an insurer or the manufacturer can require more, and the edition a jurisdiction adopted may differ from the 2023 tables here.

For a fire department the tables are the shape of its ITM program: which reports it should be receiving for each system, how often, and when a missing report means a deficiency nobody has looked at. That is a question about every protected building in the district at once, which is why it belongs on the property record rather than in a contractor's filing cabinet.

How FireInspection360 tracks it for a whole district

Contractors submit their inspection, testing and maintenance reports free of charge through the department's FireInspection360 portal. Every report lands on the property, every deficiency stays open on the record until it is corrected, the department sets the cadence it expects per system and sees which buildings are past due, and the notices go out on the department's own schedule.

See ITM report tracking in FireInspection360

See the whole platform with your own ITM program.

A one-hour walkthrough with a fire prevention expert, or the demo site right now.