Does it need a hazardous materials permit?
Pick the hazard category, its physical state and the amount. The answer is whether the 2021 International Fire Code requires an operational permit under Section 105.5, with the table row and its citation, what the code excepts, the notes whose published copies disagree, and whether NFPA 704 signs follow. What decides the answer and was not given is asked for, never guessed. Free from FireInspection360, the fire prevention platform built by fire inspectors.

Is an operational permit required?
2021 IFC Tables 105.5.9, 105.5.11 and 105.5.22 and Sections 105.5.16, 105.5.18 and 105.5.29. A permit is required only in excess of the amount the code names.
More free tools
See all 16 free toolsHazardous material classification
The 2021 IFC hazard categories for a chemical from the values its safety data sheet prints, each with the sentence that decided it, its MAQ and its permit amount.
Maximum allowable quantity calculator
The maximum allowable quantity of a hazard category per control area: the table figure, the sprinkler and cabinet increases, the story share and the Group H.
Fire extinguisher placement calculator
How many extinguishers a floor needs and how far apart, NFPA 10 Chapter 6 and OSHA 1910.157.
An operational permit starts above an amount, and the amount depends on the category, the state and sometimes the place.
Section 105.5 of the International Fire Code lists the activities that need an operational permit from the fire code official. For hazardous materials the permit turns on an amount: Table 105.5.22 names one per hazard category and physical state, and sends some categories to their own rules, compressed gases to Table 105.5.9, cryogenic fluids to Table 105.5.11, flammable and combustible liquids to Section 105.5.18, explosives to Section 105.5.16 and LP-gas to Section 105.5.29. A permit is required in excess of the amount, so the amount itself needs none, and some rows require one for any amount at all.
Some answers turn on facts beyond the category. Class I, II and IIIA liquids and cryogenic fluids have one amount inside a building and another outside; carbon dioxide in an enrichment system or a beverage dispenser has its own row; LP-gas is its own section. Where one of these decides the answer and was not given, the check tries both ways and says which question to ask. Two notes of Table 105.5.22 raise the amount for a Class 3 oxidizer kept for maintenance, and their published copies disagree on a quantity in them, so the answer points to the adopted code instead of quoting either.
The permit also decides the signs. Section 5003.5 requires NFPA 704 hazard identification signs at the entrances to where hazardous materials are stored, dispensed, used or handled in quantities requiring a permit, so the answer says whether the signs follow.